Cookie Img
Back to top
Home » Products » Powergen Online UPS » Online UPS Supermax-Series-I

Online UPS Supermax-Series-I

Online UPS Supermax-Series-I
Online UPS Supermax-Series-I
Product Code : 5KVA-30KVA
Product Description

Online UPS Supermax-Series-I

Applications:

Networking equipments, computer rooms, mission critical process, banks, offices, railways, airport, hospitals,defence and telecom centers, all type of Single Ph. Loads

Features

  • True online Double Conversion technology.
  • High end IGBT based.
  • High end Micro Controller.
  • Automatic battery charging in UPS off mode.
  • Wide Input voltage range.
  • Advanced Battery Management.
  • Short circuit and Overload Protection.
  • Parallel Redundant/Hot Standby. (optional)
  • Galvanic Isolation.
  • 1 Phase in ~ 1 Phase out (upto 10KVA)
  • 3 Phase in ~ 1 Phase out (upto 30KVA)
  • Specially Designed to suit Indian power and environment conditions.
  • Generator Compatible.
  • Over Temperature Protection.
Technical Specification

Model


SUPERMAX-SERIES-I

Capacity


5 KVA to 30 KVA

Technology


Double Conversion High Freq. Switching PWM, using IGBT's

Input

Voltage Range

160V AC~270V AC + 5V AC, Single Phase for upto 10KVA
360V AC~450V AC + 5V AC, Three Phase for upto 30KVA

Frequency

45~55Hz

Phase

Single Phase upto 10KVA and Three Phase from 5 to 30KVA

Generator Compatibility

Present

Output

Voltage

230V AC + 1%

Frequency Range

50Hz + 0.5%

THD (Linear Load)

<3%

THD (Non-Linear Load)

<5%

Overload Capability

125% for 2 minutes / 150% for 30 Seconds

Crest Factor

3:1 (max)

Short Circuit Protection

Instant

Waveform

Pure Sine Wave

Manual Bypass

Inbuilt upto 15KVA

Static Bypass (optional)

<5ms

Inverter / Overall Efficiency

85%~92%

Battery

DC Voltage

180 / 360 VDC

Mimic Control Panel

LED for UPS status and LCD for Voltage, Current & Frequency

Audible Alarm

For Battery Low/ DC High/ Output High/ Overload

Communication Interface

RS232; SNMP (optional)

Optional

Hot Stand By

Noise Level / Cooling

< 50dB / Forced Aircooled

Transient Response

For 100% Step Load charge, + 5% and recovers to normal within 20 mili-seconds.

Ambient Temperature / Relative Humidity

0-45oC / 0-95% Non-Condensing


 


POWERGEN MICRO SYSTEMS

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.